Reapter

contact us
Location: Home >Q & A
Home › News › Plate Heat Exchangers in Heat Pump Systems: Source-Side and Load-Side Selection

Plate Heat Exchangers in Heat Pump Systems: Source-Side and Load-Side Selection

Return list Reffer:Reapter
Plate Heat Exchangers in Heat Pump Systems: Source-Side and Load-Side Selection
Click number:- Release time:2026-10-26

COP is decided at the heat exchanger, not at the compressor

A heat pump's coefficient of performance is fixed by the temperature lift it has to produce, and the two heat exchangers are what actually set that lift. Compressor efficiency is largely determined once the model is chosen. The approach temperatures in the evaporator and the condenser are not, and they are usually where a specification is won or lost: a unit that holds 1 K approach on both sides will outperform a unit with a better compressor and 4 K approach on both, at every part-load point, for the whole life of the installation.

This article covers the selection logic for plate heat exchangers in hydronic and air-to-water heat pumps — how the source side and the load side differ, what the approach temperature really costs, how refrigerant-side and water-side pressure drop trade against each other, and where glycol changes the calculation. It applies to gasketed, brazed and semi-welded units alike, because the physics does not change with construction.

The two duties behave nothing alike

Engineers new to heat pumps often specify both exchangers to the same approach and the same pressure drop target. That is almost always wrong. The evaporator is a boiling duty at low temperature with a refrigerant distributing into many parallel plate channels; the condenser is a condensing duty at high temperature with a much larger temperature difference available. Their sensitivities point in opposite directions.

ParameterSource side (evaporator)Load side (condenser)
Typical secondary fluid temperature?8 °C to +25 °C (air, water, ground loop)30 °C to 55 °C flow (up to 70–90 °C on high-temperature units)
Refrigerant state changeBoiling; two-phase inlet, superheated outletCondensing; desuperheat, condense, subcool
Design approach1–3 K1–2 K
Effect of 1 K extra approachEvaporating temperature drops, lift rises, COP fallsCondensing temperature rises, lift rises, COP falls
Dominant riskRefrigerant maldistribution at part load; freezing on the water sideSubcooling loss; water-side fouling on open circuits
Usual constructionBrazed or semi-weldedBrazed, semi-welded or gasketed

The practical consequence: a small extra margin on the evaporator is cheap in plate area but expensive in COP, while the same margin on the condenser is comparatively cheaper. When a budget has to give, give it on the load side.

Approach temperature is where the COP is won or lost

Lift is the difference between condensing and evaporating temperature. Every kelvin of lift costs compressor work, and a widely used rule of thumb in the heat pump industry is that roughly 2–3 % of COP is lost per kelvin of added lift near typical operating points. Treat that as an order-of-magnitude planning figure, not a guarantee — the real sensitivity depends on refrigerant, compressor type and operating point. The direction, however, is never in doubt.

What matters for selection is that approach enters the lift twice. If the evaporator approach grows from 2 K to 4 K, the evaporating temperature must fall by roughly 2 K to deliver the same water outlet temperature, and if the condenser approach also grows by 2 K, the condensing temperature rises by 2 K. A 4 K swing in lift on a unit running at 45 °C flow with a 0 °C source is a step change in annual energy, not a rounding error — and it compounds at part load, where the compressor is least efficient.

Source-side evaporator and load-side condenser duties in a hydronic heat pump, showing the temperature lift between evaporating and condensing temperature and the approach temperature at each exchanger

Plate heat exchangers reach low approach because the flow is very close to pure counter-current and the corrugation keeps the boundary layer thin. A well-selected gasketed or brazed unit can hold 1 K; a shell-and-tube of comparable duty typically needs 5 K or more. That is the structural reason plate units dominate hydronic heat pumps rather than a matter of preference.

Refrigerant side: pressure drop costs more than it looks

On the refrigerant side, pressure drop is not merely pump or compressor penalty — it directly shifts the saturation temperature. A 30 kPa drop in the evaporator of an R32 system at low temperature can be worth nearly a kelvin of saturation change, which returns to the lift calculation above. The usual design convention is to hold evaporator refrigerant-side pressure drop below the equivalent of 0.5 K saturation temperature change, and condenser drop below 1 K.

This is where plate geometry matters. Narrow channels and small hydraulic diameter raise the heat transfer coefficient but also raise the pressure drop at a given mass flux. For a heat pump evaporator, the plate pattern and port size should be chosen so that the unit achieves the required approach at an acceptable refrigerant pressure drop — not the highest possible U-value. A very high U-value that costs 1.5 K of saturation is a net loss.

Distribution is the other half of the problem. Refrigerant entering a plate pack must split evenly across every channel; at part load, when mass flow falls well below design, maldistribution shows up as unstable superheat and hunting expansion valves. A distributor designed for the full-load condition alone is a common cause of poor part-load COP.

Water side: pressure drop costs pump energy, every hour

Secondary-side pressure drop is paid continuously by the circulator, so it belongs in the annual energy calculation, not just the datasheet. Typical design values for hydronic heat pump duties fall in the 20–60 kPa range for each exchanger; going below that usually means either larger ports or a wider plate spacing, both of which cost capital.

The more consequential decision is the design temperature difference. A 5 K spread (for example 45/40 °C) halves the flow compared with a 10 K spread and cuts pump energy sharply, but it raises the required plate area and pushes the unit toward a wider, taller frame. Modern low-temperature heating systems increasingly specify 5 K because the distribution losses and pumping energy dominate over the exchanger cost across a 15-year life.

Freeze protection: what glycol actually costs

Air-source units in cold climates and ground-loop systems in freezing ground run a glycol mixture on the source side. Two decisions follow immediately: which glycol, and how much of it.

Ethylene glycol gives slightly better heat transfer and a lower viscosity than propylene glycol at the same concentration, and it is the default for sealed, non-potable circuits. Propylene glycol is chosen where a leak could reach potable water, food or a space where toxicity matters. Both need an inhibitor package maintained over the life of the circuit — depleted inhibitors are a more common cause of corrosion in these loops than the glycol itself.

The thermal penalty is not small. A 30 % ethylene glycol solution has a freezing point around ?15 °C, but compared with water it loses roughly 20–25 % of its convective heat transfer coefficient at the same velocity, gains 20–30 % in pressure drop, and carries about 10 % less heat per unit volume because of the lower specific heat. In sizing terms that generally translates to 10–30 % more plate area for the same duty, with the exact figure depending on concentration and velocity.

Heat transfer coefficient and pressure drop penalty of ethylene glycol and propylene glycol water mixtures at 20 to 50 percent concentration, relative to water at the same flow velocity

Size the exchanger on the real mixture, not on water. A unit selected for water and then filled with 40 % glycol will not deliver its nominal duty, and the shortfall appears exactly where it hurts most — at the coldest outdoor condition, when the heat pump is already working hardest.

Brazed, semi-welded or gasketed: matching construction to the circuit

Construction choice follows from refrigerant, pressure, and whether either side will ever need mechanical cleaning.

ConstructionTypical heat pump useWatch out for
Copper-brazedSmall and mid-capacity unitary and monobloc units; HFC, HFO and R32 circuitsNot repairable; copper is attacked by ammonia; only suitable for clean, closed secondary circuits
Semi-weldedAmmonia and CO? systems; duties where the refrigerant side must stay sealed but the water side may need openingLarger footprint per unit duty; gasket on the service side still needs inspection
GasketedLarger capacities, open loops, river or well water, anywhere fouling demands accessElastomer compatibility with the secondary fluid must be checked, not assumed
All-welded / shell-and-plateHigh pressure, flammable refrigerants with tight charge limits, flooded evaporatorsNo mechanical cleaning — cleaning must be by chemical circulation

For ammonia, copper-brazed construction is not an option at all — not for reasons of preference but because ammonia attacks copper and its alloys. Propane and other flammable refrigerants push toward all-welded or semi-welded construction for a different reason: minimizing charge inside the unit reduces the refrigerant quantity that has to be managed under the applicable safety standard.

Where the secondary circuit is open — river water, cooling tower water, well water — a gasketed unit that can be opened for mechanical cleaning will usually outlast a brazed one, even at a higher first cost. For guidance on the material side of that decision, see our article on plate heat exchanger material selection from 316L to Hastelloy.

A practical selection sequence

  1. Fix the operating envelope first. Source temperature at design cold, flow temperature at design heat, and both at part load. A single design point is not an envelope, and heat pumps spend most hours away from it.
  2. Choose construction from refrigerant and secondary fluid. Ammonia excludes copper-brazed. Open circuits argue for gasketed. Flammable refrigerants push toward welded.
  3. Set approach targets per side, not globally. Evaporator 1–2 K, condenser 1–2 K for a modern hydronic unit; relax the condenser first if area must be cut.
  4. Set pressure drop budgets in saturation terms on the refrigerant side (≤0.5 K evaporator, ≤1 K condenser) and in kPa on the water side (20–60 kPa typical).
  5. Re-run the duty on the actual glycol mixture, at the lowest expected ambient, before fixing the plate count.
  6. Check part-load behaviour. Ask for the distributor turndown range and confirm the expansion valve and the plate pack are matched at 30–50 % load, not only at rated capacity.

Two further checks belong on that list for projects with seasonal load profiles: whether the exchanger tolerates reverse operation in defrost, and whether the water side can be drained or is protected by trace heating during a standstill. Our article on variable flow and part-load operation covers the control-side implications.

Common questions

What approach temperature should I specify for a heat pump? For a hydronic heat pump, 1–2 K on both sides is achievable with plate heat exchangers and is where good designs land. Below 1 K the plate area and cost rise steeply for a small COP gain; above 3 K you are leaving measurable energy on the table every hour of operation.

Can a brazed plate heat exchanger be used with ammonia? No. Ammonia attacks copper and copper alloys, so copper-brazed units are excluded. Use semi-welded or all-welded construction with stainless plates.

How much extra area does glycol need? Plan on 10–30 % more plate area than a water-based selection for the same duty, depending on concentration and velocity — 30 % ethylene glycol typically sits around the lower half of that range and 50 % toward the top.

Why does my unit lose capacity in cold weather? Usually two effects together: the source temperature falls, which lowers the evaporating temperature, and if the source circuit is glycol, the mixture's higher viscosity further reduces the heat transfer coefficient. Both were in the design data — but only if the exchanger was sized on the mixture rather than on water.

Is a shell-and-tube acceptable instead? It can be, and for flooded evaporators it is often the standard choice. The trade is approach: shell-and-tube units typically need 5 K or more, which is difficult to reconcile with a high-COP heat pump specification. Our comparison of plate and shell versus shell and tube sets out the boundary.

Conclusion

The heat exchanger is the part of a heat pump where the COP is either protected or quietly given away, and most of the decision is made in four numbers: approach on each side, pressure drop on each side. Get those right on the real fluid at the real cold-day condition and the rest of the specification follows.

Reapter supplies gasketed, brazed and semi-welded plate heat exchangers for heat pump duties, selected against the actual mixture and the full operating envelope rather than a single rated point. If you have a duty to check, send the source and load temperatures, flows, refrigerant and glycol concentration — we will run the selection and show the approach and pressure drop you would get. Request a selection review.

Relevant article

Latest information